Applications
It can be used for fixed installation indoors and outdoors in cable ducts or directly in the ground. These cables are provided with mechanical protection and are therefore suitable for external use, direct burial and areas where sudden mechanical stress are expected.
Features
• Working temperature:
• Max. conductor temperature at normal operation: 90℃
• Max. conductor temperature at short circuit(Max. 5s duration): 250℃
• Voltage:
• AC 0.6/1KV
• Test voltage:
• AC 3.5KV for 5min, not break down
Standards
IEC60502-1, BS5467
single core copper cables
Size mm2 |
Insulation Thicknessmm |
Inner-sheath Thicknessmm |
armour wire Thicknessmm |
Outer-sheath Thicknessmm |
Approx.Diameter ofcable mm |
Max. DC resistanceat 20C (Ω/km) |
1.5 | 0.7 | 1.2 | 0.2 | 1.8 | 10.8 | 12.1 |
2.5 | 0.7 | 1.2 | 0.2 | 1.8 | 11.2 | 7.41 |
4 | 0.7 | 1.2 | 0.2 | 1.8 | 11.7 | 4.61 |
6 | 0.7 | 1.2 | 0.2 | 1.8 | 12.2 | 3.08 |
10 | 0.7 | 1.2 | 0.2 | 1.8 | 13.2 | 1.83 |
16 | 0.7 | 1.2 | 0.2 | 1.8 | 14.2 | 1.15 |
25 | 0.9 | 1.2 | 0.2 | 1.8 | 15.8 | 0.727 |
35 | 0.9 | 1.2 | 0.2 | 1.8 | 16.8 | 0.524 |
50 | 1 | 1.2 | 0.2 | 1.8 | 18.4 | 0.387 |
70 | 1.1 | 1.2 | 0.2 | 1.8 | 20.2 | 0.268 |
95 | 1.1 | 1.2 | 0.2 | 1.8 | 21.8 | 0.193 |
120 | 1.2 | 1.2 | 0.2 | 1.8 | 23.4 | 0.153 |
150 | 1.4 | 1.2 | 0.2 | 1.8 | 25.4 | 0.124 |
185 | 1.6 | 1.2 | 0.2 | 1.8 | 27.4 | 0.0991 |
240 | 1.7 | 1.2 | 0.5 | 2 | 31.4 | 0.0754 |
300 | 1.8 | 1.2 | 0.5 | 2 | 33.8 | 0.0601 |
400 | 2 | 1.2 | 0.5 | 2.2 | 37.8 | 0.047 |
500 | 2.2 | 1.2 | 0.5 | 2.3 | 41.2 | 0.0366 |
630 | 2.4 | 1.3 | 0.5 | 2.4 | 45.3 | 0.0283 |
2 core copper cables
No. of conductor |
Size mm2 |
Insulation Thickness mm |
Inner-sheath Thickness mm |
armour wire Thickness mm |
Outer-sheath Thickness mm |
Approx. Diameter of cable mm |
Max. DC resistance at 20C (Ω /km) |
2 | 1.5 | 0.7 | 1.2 | 0.2 | 1.8 | 13.6 | 12.1 |
2 | 2.5 | 0.7 | 1.2 | 0.2 | 1.8 | 14.4 | 7.41 |
2 | 4 | 0.7 | 1.2 | 0.2 | 1.8 | 15.4 | 4.61 |
2 | 6 | 0.7 | 1.2 | 0.2 | 1.8 | 16.4 | 3.08 |
2 | 10 | 0.7 | 1.2 | 0.2 | 1.8 | 18.4 | 1.83 |
2 | 16 | 0.7 | 1.2 | 0.2 | 1.8 | 20.4 | 1.15 |
2 | 25 | 0.9 | 1.2 | 0.2 | 1.8 | 23.6 | 0.727 |
2 | 35 | 0.9 | 1.2 | 0.2 | 1.8 | 27 | 0.524 |
2 | 50 | 1 | 1.2 | 0.2 | 1.8 | 24.7 | 0.387 |
2 | 70 | 1.1 | 1.2 | 0.2 | 1.8 | 27.4 | 0.268 |
2 | 95 | 1.1 | 1.2 | 0.5 | 2 | 31.6 | 0.193 |
2 | 120 | 1.2 | 1.2 | 0.5 | 2.1 | 34.7 | 0.153 |
2 | 150 | 1.4 | 1.2 | 0.5 | 2.2 | 37.9 | 0.124 |
2 | 185 | 1.6 | 1.2 | 0.5 | 2.3 | 41.4 | 0.0991 |
2 | 240 | 1.7 | 1.3 | 0.5 | 2.4 | 45.4 | 0.0754 |
2 | 300 | 1.8 | 1.4 | 0.5 | 2.6 | 49.9 | 0.0601 |
2 | 400 | 2 | 1.5 | 0.5 | 2.8 | 55.8 | 0.047 |
3 core copper cables
No. of conductor |
Size mm2 |
Insulation Thickness mm |
Inner-sheath Thickness mm |
armour tape Thickness mm |
Outer-sheath Thickness mm |
Approx. Diameter of cable mm |
Max. DC resistance at 20C (Ω /km) |
3 | 1.5 | 0.7 | 1.2 | 0.2 | 1.8 | 14 | 12.1 |
3 | 2.5 | 0.7 | 1.2 | 0.2 | 1.8 | 14.9 | 7.41 |
3 | 4 | 0.7 | 1.2 | 0.2 | 1.8 | 16 | 4.61 |
3 | 6 | 0.7 | 1.2 | 0.2 | 1.8 | 17.1 | 3.08 |
3 | 10 | 0.7 | 1.2 | 0.2 | 1.8 | 19.2 | 1.83 |
3 | 16 | 0.7 | 1.2 | 0.2 | 1.8 | 21.4 | 1.15 |
3 | 25 | 0.9 | 1.2 | 0.2 | 1.8 | 24.6 | 0.727 |
3 | 35 | 0.9 | 1.2 | 0.2 | 1.9 | 28.7 | 0.524 |
3 | 50 | 1 | 1.2 | 0.2 | 1.9 | 28.2 | 0.387 |
3 | 70 | 1.1 | 1.2 | 0.5 | 2 | 33.4 | 0.268 |
3 | 95 | 1.1 | 1.2 | 0.5 | 2.1 | 36.6 | 0.193 |
3 | 120 | 1.2 | 1.2 | 0.5 | 2.2 | 40.1 | 0.153 |
3 | 150 | 1.4 | 1.3 | 0.5 | 2.4 | 44.5 | 0.124 |
3 | 185 | 1.6 | 1.4 | 0.5 | 2.5 | 48.8 | 0.0991 |
3 | 240 | 1.7 | 1.5 | 0.5 | 2.7 | 54.1 | 0.0754 |
3 | 300 | 1.8 | 1.6 | 0.5 | 2.9 | 59.3 | 0.0601 |
3 | 400 | 2 | 1.7 | 0.5 | 3 | 64.3 | 0.047 |
4 core copper cables
No. of conductor |
Size mm2 |
Insulation Thickness mm |
Inner-sheath Thickness mm |
armour tape Thickness mm |
Outer-sheath Thickness mm |
Approx. Diameter of cable mm |
Max. DC resistance at 20c ( 0 /km) |
4 | 1.5 | 0.7 | 1.2 | 0.2 | 1.8 | 14.8 | 12.1 |
4 | 2.5 | 0.7 | 12 | 0.2 | 1.8 | 15.7 | 7.41 |
4 | 4 | 0.7 | 1.2 | 0.2 | 1.8 | 17 | 4.61 |
4 | 6 | 0.7 | 12 | 0.2 | 1.8 | 18.2 | 3.08 |
4 | 10 | 0.7 | 1.2 | 0.2 | 1.8 | 20.6 | 1.83 |
4 | 16 | 0.7 | 12 | 0.2 | 1.8 | 23 | 1.15 |
4 | 25 | 0.9 | 1.2 | 0.2 | 1.8 | 26.9 | 0.727 |
4 | 35 | 0.9 | 1.2 | 0.5 | 2 | 32.6 | 0.524 |
4 | 50 | 1 | 1.2 | 0.5 | 2 | 32.3 | 0.387 |
4 | 70 | 1.1 | 12 | 0.5 | 2.1 | 36.6 | 0.268 |
4 | 95 | 1.1 | 1.2 | 0.5 | 2.3 | 40.6 | 0.193 |
4 | 120 | 1.2 | 1.3 | 0.5 | 2.4 | 44.9 | 0.153 |
4 | 150 | 1.4 | 1.4 | 0.5 | 2.6 | 49.5 | 0.124 |
4 | 185 | 1.6 | 1.5 | 0.5 | 2.7 | 54.7 | 0.0991 |
4 | 240 | 1.7 | 1.6 | 0.5 | 2.9 | 60.8 | 0.0754 |
4 | 300 | 1.8 | 1.7 | 0.5 | 3.1 | 66.5 | 0.0601 |
4 | 400 | 2 | 1.9 | 0.5 | 3.4 | 75.8 | 0.047 |
5 core copper cables
No. of conductor |
Size mm2 |
Insulation Thickness mm |
Inner-sheath Thickness mm |
armour tape ThicknGSS mm |
Outersheath Thickness mm |
Approx. Diameter of cable mm |
Max. DC resistance at 20C( Q /km) |
5 | 1.5 | 0.7 | 1.2 | 0.2 | 1.8 | 15.6 | 12.1 |
5 | 2.5 | 0.7 | 1.2 | 0.2 | 1.8 | 16.6 | 7.41 |
5 | 4 | 0.7 | 1.2 | 0.2 | 1.8 | 18 | 4.61 |
5 | 6 | 0.7 | 1.2 | 0.2 | 1.8 | 19.3 | 3.08 |
5 | 10 | 0.7 | 1.2 | 0.2 | 1.8 | 22 | 1.83 |
5 | 16 | 0.7 | 1.2 | 0.2 | 1.8 | 24.7 | 1.15 |
5 | 25 | 0.9 | 1.2 | 0.2 | 1.9 | 29.3 | 0.727 |
5 | 35 | 0.9 | 1.2 | 0.5 | 2.1 | 35.5 | 0.524 |
5 | 50 | 1 | 1.2 | 0.5 | 2.1 | 35.1 | 0.387 |
5 | 70 | 1.1 | 1.2 | 0.5 | 2.2 | 39.7 | 0.268 |
5 | 95 | 1.1 | 1.3 | 0.5 | 2.4 | 44.5 | 0.193 |
5 | 120 | 1.2 | 1.4 | 0.5 | 2.5 | 48.8 | 0.153 |
5 | 150 | 1.4 | 1.5 | 0.5 | 2.7 | 54.3 | 0.124 |
5 | 185 | 1.6 | 1.6 | 0.5 | 2.9 | 59.9 | 0.0991 |
5 | 240 | 1.7 | 1.7 | 0.5 | 3.1 | 66.5 | 0.0754 |
5 | 300 | 1.8 | 1.8 | 0.5 | 3.3 | 72.8 | 0.0601 |
5 | 400 | 2 | 2 | 0.8 | 3.7 | 85.8 | 0.047 |
3+1 cores cables
No. Of conductor |
Size mm2 |
No. of conductor |
Stee mm2 |
Insulation Thickness mm |
Inner-sheath Thickness mm |
armour tape Thickness mm |
Outer. sheath Thickness mm |
Approx. Diameter of cabb mm |
Max. DC resistance M20C( 0 /km) |
|
3 | 1.5 | 1 | 1 | 0.7 | 1.2 | 0.2 | 1.8 | 15.6 | 12.1 | |
3 | 2.5 | 1 | 1.5 | 0.7 | 1.2 | 0.2 | 1.8 | 16.6 | 7.41 | |
3 | 4 | 1 | 2.5 | 0.7 | 1.2 | 0.2 | 1.8 | 18 | 4.61 | |
3 | 6 | 1 | 4 | 0.7 | 1.2 | 0.2 | 1.8 | 19.3 | 3.08 | |
3 | 10 | 1 | 6 | 0.7 | 1.2 | 0.2 | 1.8 | 22 | 1.83 | |
3 | 16 | 1 | 10 | 0.7 | 1.2 | 0.2 | 1.8 | 24.7 | 1.15 | |
3 | 25 | 1 | 16 | 0.9 | 1.2 | 0.2 | 1.8 | 29.3 | 0.727 | |
3 | 35 | + | 1 | 16 | 0.9 | 1.2 | 0.5 | 2 | 35.5 | 0.524 |
3 | 50 | + | 1 | 25 | 1 | 1.2 | 0.5 | 2 | 35.1 | 0.387 |
3 | 70 | + | 1 | 35 | 1.1 | 1.2 | 0.5 | 2.1 | 39.7 | 0.268 |
3 | 95 | ♦ | 1 | 50 | 1.1 | 1.2 | 0.5 | 2.3 | 44.5 | 0.193 |
3 | 120 | 1 | 70 | 1.2 | 1.3 | 0.5 | 2.4 | 48.8 | 0.153 | |
3 | 150 | ♦ | 1 | 70 | 1.4 | 1.4 | 0.5 | 2.6 | 54.3 | 0.124 |
3 | 185 | 1 | 95 | 1.6 | 1.5 | 0.5 | 2.7 | 59.9 | 0.0991 | |
3 | 240 | 1 | 120 | 1.7 | 1.6 | 0.5 | 2.9 | 66.5 | 0.0754 | |
3 | 300 | + | 1 | 150 | 1.8 | 1.7 | 0.5 | 3.1 | 72.8 | 0.0601 |
3 | 400 | 1 | 185 | 2 | 1.9 | 0.5 | 3.4 | 85.8 | 0.047 |
3+2 cores cables
NO. Of conductor |
Size mm2 |
+ |
No. of conductor |
Size mm2 |
Insulation Thickness mm |
Inner-sheath Thickness mm |
armour tape Thickness mm |
Outer-s heath Thickness mm |
Approx Diameter of cable mm |
Max. DC resistance at 20C( Q /km) |
3 | 1.5 | + | 2 | 1 | 0.7 | 1.2 | 0.2 | 1.8 | 15.2 | 12.1 |
3 | 2.5 | + | 2 | 1.5 | 0.7 | 1.2 | 0.2 | 1.8 | 16.3 | 7.41 |
3 | 4 | + | 2 | 2.5 | 0.7 | 1.2 | 0.2 | 1.8 | 17.5 | 4.61 |
3 | 6 | + | 2 | 4 | 0.7 | 1.2 | 0.2 | 1.8 | 18.8 | 3.08 |
3 | 10 | + | 2 | 6 | 0.7 | 1.2 | 0.2 | 1.8 | 21.4 | 1.83 |
3 | 16 | + | 2 | 10 | 0.7 | 1.2 | 0.2 | 1.8 | 24 | 1.15 |
3 | 25 | + | 2 | 16 | 0.9 | 1.2 | 0.2 | 1.9 | 28.3 | 0.727 |
3 | 35 | + | 2 | 16 | 0.9 | 1.2 | 0.5 | 2.1 | 34.3 | 0.524 |
3 | 50 | + | 2 | 25 | 1 | 1.2 | 0.5 | 2.1 | 35.1 | 0.387 |
3 | 70 | + | 2 | 35 | 1.1 | 1.2 | 0.5 | 2.2 | 39.7 | 0.268 |
3 | 95 | + | 2 | 50 | 1.1 | 1.3 | 0.5 | 2.4 | 44.5 | 0.193 |
3 | 120 | + | 2 | 70 | 1.2 | 1.4 | 0.5 | 2.5 | 48.8 | 0.153 |
3 | 150 | + | 2 | 70 | 1.4 | 1.5 | 0.5 | 2.7 | 54.3 | 0.124 |
3 | 185 | + | 2 | 95 | 1.6 | 1.6 | 0.5 | 2.9 | 59.9 | 0.0991 |
3 | 240 | + | 2 | 120 | 1.7 | 1.7 | 0.5 | 3.1 | 66.5 | 0.0754 |
3 | 300 | + | 2 | 150 | 1.8 | 1.8 | 0.5 | 3.3 | 72.8 | 0.0601 |
3 | 400 | + | 2 | 185 | 2 | 2 | 0.8 | 3.7 | 85.8 | 0.047 |
4+1 cores cables
No. of conductor |
Size mm2 |
+ |
No. of conductor |
Size mm2 |
Insulation Thickness mm |
Inner-sheath Thickness mm |
armour tape Thickness mm |
Outersheath Thickness mm |
Approx. Diameter of cabto mm |
Max. DC resistance at 20c ( Q /km) |
4 | 1.5 | + | 1 | 1 | 0.7 | 1.2 | 0.2 | 1.8 | 15.4 | 12.1 |
4 | 2.5 | + | 1 | 1.5 | 0.7 | 1.2 | 0.2 | 1.8 | 16.5 | 7.41 |
4 | 4 | + | 1 | 2.5 | 0.7 | 1.2 | 0.2 | 1.8 | 17.8 | 4.61 |
4 | 6 | + | 1 | 4 | 0.7 | 1.2 | 0.2 | 1.8 | 19.1 | 3.08 |
4 | 10 | + | 1 | 6 | 0.7 | 1.2 | 0.2 | 1.8 | 21.8 | 1.83 |
4 | 16 | + | 1 | 10 | 0.7 | 1.2 | 0.2 | 1.8 | 24.4 | 1.15 |
4 | 25 | + | 1 | 16 | 0.9 | 1.2 | 0.2 | 1.9 | 28.9 | 0.727 |
4 | 35 | + | 1 | 16 | 0.9 | 1.2 | 0.5 | 2.1 | 35 | 0.524 |
4 | 50 | + | 1 | 25 | 1 | 1.2 | 0.5 | 2 | 32.7 | 0.387 |
4 | 70 | + | 1 | 35 | 1.1 | 1.2 | 0.5 | 2.2 | 37.3 | 0.268 |
4 | 95 | + | 1 | 50 | 1.1 | 1.3 | 0.5 | 2.3 | 41.9 | 0.193 |
4 | 120 | + | 1 | 70 | 1.2 | 1.3 | 0.5 | 2.4 | 45.8 | 0.153 |
4 | 150 | + | 1 | 70 | 1.4 | 1.4 | 0.5 | 2.6 | 50.8 | 0.124 |
4 | 185 | + | 1 | 95 | 1.6 | 1.5 | 0.5 | 2.8 | 56 | 0.0991 |
4 | 240 | + | 1 | 120 | 1.7 | 1.6 | 0.5 | 3 | 62.3 | 0.0754 |
4 | 300 | + | 1 | 150 | 1.8 | 1.7 | 0.5 | 3.2 | 68.4 | 0.0601 |
4 | 400 | + | 1 | 185 | 2 | 1.9 | 0.5 | 3.5 | 79 | 0.047 |
1. Conductor: Plain annealed copper or aluminium wires, class 2, conforms to IEC60228.
Available in single-core and multiple-core versions.
For multi-cores, the conductor is sector shape for section area bigger than 35mm2.
Tinned copper wire is optional.
2. Insulation: XLPE (Cross-linked polyethylene).
3. Inner sheath: PVC (polyvinyl chloride). LSZH, PE is optional.
4. Amour: aluminium tape (ATA) for single core cable
Galvanized steel tape (STA) for multi-core
5. Outer-sheath: PVC (polyvinyl chloride).
Flame retardant is optional;
PE is optional;
LSZH is optional.