Application
Medium voltage aluminium cable, HEPR insulation, halogen-free sheath, for the transmission and distribution of energy in medium voltage networks
Electrical Characteristics
Service temperature in fixed and protected installation: -15 °C to +70 °C
Service voltage: 18/30kV (36kV)
Temperature during handling, transport and storage: +5 °C to +50 °C
Max. conductor temperature: +105 °C
Max. temperature in short circuit (max. 5 sec) : +250 °C
Standards
UNE-HD 620-9E
Size(mm2) | Conductor Diameter(mm) | Overall Diameter(mm) | Weight(kg/km) | Max. DC resistance at 20C (Ω/km) |
1X50/16* | 18,0 | 26,2 | 790 | 0.641 |
1X95/16 | 20,8 | 29,0 | 980 | 0.320 |
1X150/16* | 23,5 | 32,0 | 1205 | 0.206 |
1X240/16* | 27,6 | 36,1 | 1570 | 0.125 |
1X400/16* | 32,8 | 41,4 | 2115 | 0.0778 |
1X500/16 | 36,2 | 44,5 | 2625 | 0.0605 |
1X630/16* | 40,8 | 49,4 | 3075 | 0.0469 |
Conductor:Stranded aluminium strands, circular and compacted, Class 2 IEC/EN60228
Insulation:Internal semi conductor - HEPR - Semi detachable external conductor. Applied by simultaneous triple extrusion
Overall cable shield:Annealed copper wire core, arranged in open helix + copper strap
Identification:Natural
Sheath:Polyolefin